RecallWatchUSA

Home / Recalls / Fire & Safety

CPSC, Kidde Announce Recall of Industrial Fire Extinguishers

Recalled July 26, 2005 · CPSC recall 05589 · Kidde

Affected model - Remove from serviceNon-affected model - Leave in serviceExtinguisher Height Comparison
Hazard
The nylon valves on these extinguishers can separate from the steel cylinder during the 6-year recharge service or shortly afterwards, creating a safety hazard to fire extinguisher service personnel and consumers.
Remedy
Fire Extinguisher Distributors and Service Organizations must immediately stop servicing all units covered under this Alert. Kidde has instituted a Fire Extinguisher Replacement Program ("Replacement Program") for all units covered by this Alert. If you are a Fire Extinguisher Distributor or Service Organization and you have not already received a copy of the Replacement Program, as outlined in Service Bulletin 007, please contact Kidde. Only professional Fire Extinguisher Distributors and Service Organizations should remove the affected units and the steps as outlined in the Replacement Program must be followed.
Units
About 470,000
Incidents / injuries
Kidde has received five reports of valve separation during either technical service of the units or shortly afterwards, resulting in three reports of injuries.

Description

This Alert involves all Kidde 10 lb. dry chemical fire extinguishers manufactured with a black plastic Zytel® nylon valve assembly and a steel cylinder, between 1991 and 2000. These units were the subject of Kidde Service Bulletin 007 issued on July 21, 2004. These units were designed for commercial and industrial applications, and the majority of these units were placed into service in factories, plants, businesses and other commercial locations, as they require service by a qualified Fire Extinguisher Distributor or Service Organization every 6 years. Some of these units are in use in residential settings. The affected extinguishers have a steel cylinder with a welded neck ring and are between 19 to 21 inches tall, as depicted in the image below. This Alert does not apply to Kidde's smaller 2 1/2 and 5 lb. residential fire extinguishers.

What to do

Fire Extinguisher Distributors and Service Organizations must immediately stop servicing all units covered under this Alert. Kidde has instituted a Fire Extinguisher Replacement Program ("Replacement Program") for all units covered by this Alert. If you are a Fire Extinguisher Distributor or Service Organization and you have not already received a copy of the Replacement Program, as outlined in Service Bulletin 007, please contact Kidde. Only professional Fire Extinguisher Distributors and Service Organizations should remove the affected units and the steps as outlined in the Replacement Program must be followed.

Contact

Fire Extinguisher Distributors and Service Organizations should contact Kidde at 1-877-777-8170 between 8 AM and 5 PM ET Monday through Friday to participate in Kidde's Replacement Program. Only professional Fire Extinguisher Distributors and Service Organizations should call this number. Consumers who suspect that they may possess one of the industrial units covered by this Alert should not remove the unit and should contact Kidde at (800) 631-7377 between 8 AM and 5 PM ET Monday through Friday. Units should not be returned to the place of purchase. More information can also be obtained by visiting Kidde's Web site at www.kiddeus.com and referencing Kidde Service Bulletin 007 and Recall Alert.

Product
Kidde 10 lb. industrial dry chemical fire extinguishers with black plastic Zytel® nylon valves in steel cylinders manufactured between 1991 and 2000
Manufacturer(s)
Walter Kidde Portable Equipment Inc., of Mebane, N.C.
Retailers
Commercial fire equipment distributors and stores nationwide, between 1991 and 2000.
Made in
United States

Source: U.S. Consumer Product Safety Commission. Official recall notice on cpsc.gov →