RecallWatchUSA

Home / Recalls / Fire & Safety

CPSC, AnnounceGE Security Inc. Retrofit/Recall of Smoke Detector Systems

Recalled December 22, 2004 · CPSC recall 05526 · GE Security

Recalled smoke detectorControl panel of recalled smoke detectorWarning label on recalled smoke detector
Hazard
The smoke alarms can fail to activate during a fire or emergency, if installed in combination with certain control panels.
Remedy
Consumers should contact their system installer or service provider to arrange for a free repair or replacement to make the smoke detectors and control panel systems compatible.
Units
Approximately 246,800 smoke detectors
Incidents / injuries
None reported.

Description

The recalled smoke detection systems involve hard-wired S10A ESL smoke detectors that are incompatible with certain ITI control panels as well as certain S09A/S10A listed ESL smoke detectors that may be incompatible with control panels from other manufacturers. Model numbers are printed on the back of the smoke detectors. Inside the ITI control panel is a label that lists the name and model number of the unit. The following model names and model numbers of ITI control panels are incompatible when installed with the following model numbers of ESL smoke detectors: Smoke Detector Model Numbers 429C 429CT 511C 521B (when SW1 is OFF) 521BXT (when SW1 is OFF) 521NB* 521NBXT* 521NCSXT 711U 711UT 721U 721UT *In addition, the models 521NB and 521NBXT detectors, if installed in the S09A configuration, may self-adjust to an S10A configuration. Thus, these two model detectors may not be compatible with other manufacturer's control panels that are only S09A compatible. ITI Control Panel Model Names and Model Numbers Concord: 60-734-01 60-801 60-801-01 60-792-01-95R-16Z 60-792-01-95R-32Z 60-792-95R-32Z Advent: 60-562 (-01 through -06) Concord Express: 60-806-95R-16Z 60-806-95R

What to do

Consumers should contact their system installer or service provider to arrange for a free repair or replacement to make the smoke detectors and control panel systems compatible.

Contact

Call UTC Fire and Security (formerly GE Security) at 855-286-8889 option 2 between 8am and 8pm ET Monday through Friday.

Product
Smoke Detector Systems
Manufacturer(s)
GE Security Inc., of Austin, Texas
Retailers
Distributors, dealers and installers of security systems nationwide, from June 2002 through October 2004. The smoke detectors and the control panels were sold separately as individual components, and were also sold together as part of a security system for between $180 and $1,150.
Made in
United States

Source: U.S. Consumer Product Safety Commission. Official recall notice on cpsc.gov →