Carrier® Recalls to Repair Commercial Rooftop HVAC Units Due to Fire Hazard (Recall Alert)

Recalled March 19, 2018 · CPSC recall 18731 · Carrier®

40/50 series LC rooftop HVAC unit
Hazard
The HVAC's humidimizer fan can fail to shut off when a connected smoke detector is tripped, posing a fire hazard.
Remedy
Repair
Units
About 530
Incidents / injuries
Carrier has received one report of a fan not shutting off during installation testing. No injuries have been reported.

Description

This recall involves Carrier WeatherExpert 6-23 ton, 48/50 series, light commercial rooftop HVAC units intended for use in commercial and institutional buildings and that have a factory installed dehumidification feature. The model numbers are 48/50LC07-26 with an A in the 6th digit and a 0 (zero) in the 14th digit of the model number (e.g., 48LCTA24F2M5-0S1B3). Note that dashes should be counted as digits in the model number. The serial numbers are 1214P to 3317P. The model and serial number can be found on the unit rating plate located on the back of the unit.

What to do

Purchasers should immediately contact their Carrier dealer for a free repair, which consists of free replacement and installation of the electronic control board. The firm is contacting all known purchasers.

Contact

Carrier toll-free at 844-864-8748 from 8 a.m. to 5 p.m. ET Monday through Friday, or online at www.carrier.com and click on “Product Safety Recall” to locate a local Carrier dealer for more information.

Product
Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option
Manufacturer(s)
Carrier México, S.A. de C.V.
Imported by
Carrier Corporation, of Jupiter, Fla.
Retailers
Carrier distributors nationwide from March 2014 to September 2017 for between $25,000 and $93,000.
Made in
Mexico

Source: U.S. Consumer Product Safety Commission. Official recall notice on cpsc.gov →